Brand: Bently Nevada Description: 164578-01 Condition: Brand New Certificate: COO TEST REPORT WARRANTY LETTER Warranty: 1 year Inventory Qty: 9 Payment Term: T/T Shipping Port: Shenzhen Bently Nevada 164578-01 Designed for integration into Bently Nevada 3500/3700 Series rack systems to interface field-mounted combustible or toxic gas sensors.
Manufacture |
Bently Nevada |
Model Number |
164578-01 |
Ordering Number |
164578-01 |
Catalog |
3500/63 |
Description |
Gas Sensor Internal Termination Input/Output Module |
Country Of Origin |
USA |
HS CODE |
85389091 |
Dimension |
24*2.4*10 (CM) |
Weight |
1.2 kg |
Ordering Information
HAZARDOUS GAS DETECTION MODULE
3500/63-AXX-BXX
A: Input/Output Module:
01 Internal Termination Catalytic Bead Input/Output Module
02 External Termination Catalytic Bead Input/Output Module
B: Agency Approvals:
01 FM(C/US), IEC
Technical Parameters
Channels: 4 analog inputs for Bently Nevada 164578-01, individually configurable for:
4–20 mA current loops
0–10 V DC voltage signals
Internal Terminations:
250 Ω precision resistors for 4–20 mA
10 kΩ input impedance for voltage mode
Intrinsic-Safety Barriers: Internal zener-diode networks per input rated for Class I Zone 2/Div 2 in Bently Nevada 164578-01
Resolution & Accuracy: 16-bit A/D, ± 0.1 % of full-scale
Sampling Rate: 50 samples/sec per channel
Isolation: ≥ 1 kV channel-to-chassis ground
Input Protection: Overvoltage clamp to ± 35 V, reverse-polarity protection
Power Consumption: 24 V DC (18–32 V DC) via rack bus; ≤ 3 W
Environmental Ratings:
Operating Temp: 0 °C to +60 °C
Storage Temp: –40 °C to +85 °C
Humidity: up to 95 % RH, non-condensing
Product function
Signal Conditioning: Accepts low-level analog outputs, applies termination and barrier isolation via Bently Nevada 164578-01, then digitizes for rack-bus transmission.
Integrated Barriers & Terminations: Embeds safety barriers and input resistances on-board.
Diagnostics: Monitors loop integrity and reports faults over the digital bus.
Application Areas
Combustible-Gas Detection: Monitoring methane concentrations using Bently Nevada 164578-01 in turbine enclosures.
Toxic-Gas Safety Systems: Integrating H₂S/CO detectors into shutdown logic.
Hazardous-Area Installations: Zone 2/Div 2 control panels with Bently Nevada 164578-01.
Process-Safety Integration: Feeding gas-sensor data to DCS/SCADA systems.