Brand: GE Description: Discrete Relay Output Module Condition: Brand New Certificate:COO TEST REPORT WARRANTY LETTER Warranty: 1 year Inventory Qty: 7 Payment Term: T/T Shipping Port: ShenZhen GE IC697MDL940 is a 16-point relay output module designed for the 90-70 Series PLC system. It provides reliable control of low to medium power loads using 8 Form C (SPDT) relays and 8 Form A (SPST) relays.
Manufacture |
GE |
Model Number |
IC697MDL940 |
Ordering Number |
IC697MDL940 |
Catalog |
90-70 |
Country Of Origin |
USA |
HS CODE |
85389091 |
Dimension |
13cm x 7cm x 4.5cm |
Packing Dimension |
15cm x 9cm x 7cm |
Weight |
0.8kg |
Operating Parameters
Rated Voltage: 120/240 VAC or 5/24/125 VDC.
Number of Outputs: 16 outputs, comprising 8 isolated Form C (SPDT) relays and 8 Form A (SPST) relays.
Maximum Load Current:
2 Amps per point at 120/240 VAC or 24 VDC.
0.2 Amps per point at 125 VDC.
Power Consumption: Draws 750 mA from the 5V bus on the backplane.
Switching Frequency: Up to 20 cycles per minute for inductive loads.
Minimum Load: 10 mA to ensure reliable operation.
Isolation Voltage: 1500 Volts between field side and logic side, providing robust isolation.
Product Features
Relay Outputs: 8 Form C and 8 Form A relay outputs for controlling a variety of field devices.
Protection:Output circuit equipped RC snubber circuits, shock resistance. Per point flash is integrated as an overcurrent protection element.
No External Power Required: Powered by module only, no need power from external.
Operations on High-Speed Signals: GE IC697MDL940 is developed to perceive a huge number of digital and analog signals instantly. In complex industrial automation setups, multiple sensors and actuators often need to communicate back and forth. It is able to receive signals from different devices and turn them into operational commands
Versatile I/O Configuration: The input and output channels are adjustable. Users can modify the configurations as per their application needs. GE IC697MDL940 provides flexibility, whether it be digital I/O for discrete control or analog I/O for continuous variable monitoring.
Fault Tolerance and Redundancy: Equipped with certain fault-tolerant mechanisms, it can detect errors present in signals or internal components. If there is a noticeable failure, GE IC697MDL940 is capable of continuing with limited function or sounding alarms for the operator. Control system reliability is aided by redundancy features.
Installation
Preparation:Ensure that the PLC rack is powered off before installation to prevent electrical hazards. However the module must be for an empty slot in the Series 90-70 PLC rack.
To mount: Hold the module above the target slot and hard push it down until you hear a click or you feel it far down. Retain the module, using either the manpower or locking mechanism, to avoid dislodging or earthquakes.
Field Wiring:Of course, if the given installer has a removable terminal board for connecting field devices, make sure to do all connections securely. Refer to the wiring diagram in the user manual to ensure proper polarity and operation.
Power-Up:Once installation and wiring is complete, power up the PLC rack. Check the module's status lights to ensure it is working properly.
Application Range
Automotive Manufacturing: In automotive production plants, GE IC697MDL940 is utilized for controlling robotic welding machinery, assembly line conveyors, and quality inspection systems. By coordinating the way that these components function, it helps with the efficient production of vehicles.
Aerospace Industry:Able to manage the control of precision machinery and instrumentation for the aerospace manufacturing and testing GE IC697MDL940 observes and regulates variables like pressure, temperature, and position in settings where precision and dependability are crucial.
Industrial Robotics:GE IC697MDL940 serves as an interface between the robot controller and external sensors and actuators in the robotic workcell. This allows the robot to adapt to changes in the environment and execute intricate tasks with great accuracy.
Troubleshooting
Module Not Responding:Verify that the module is correctly installed and securely seated in the PLC rack.Check the power supply to ensure the PLC rack is energized.
Output Channel Failure:Check field wiring for loose connections or wiring mistakes Verify that the connected field device is working correctly. Check the relevant fuse for the output that's out and replace if it's blown.
Intermittent Operation:Ensure that the load connected to each output does not exceed the specified current ratings.Inspect for environmental factors such as excessive vibration or temperature extremes that may affect performance.Review the switching frequency to ensure it is within the module's capabilities, especially for inductive loads.